GENERAL FEATURES

  • Standard ratings from 17.5 t 537.5kVAr
  • Standard sizes according to capacitor ratings
  • Stand alone unit connected by cables or connected to extended main busbars
  • Capacitors fitted with protection caps
  • Temperature controlled by fan
  • Special fixing brackets for the capacitors resulting in increased air circulation
  • Protection class IP 41 to IP 54

TECHNICAL DATA

INCOMER MCCB 40A to 1250A, 3-pole, 30 to 85kA Load Break Switch 40A to 1250A, 3-pole
OUTGOINGS HRC - Fuses, 100kA
BUS BARS H.C.H.D. copper, electrolytically tinned rated for 50kA short circuit
CONTRACTORS Rated for the size of the capacitors, special contactors for power factor correction capacitors equipped with limiting resistance for the inrush current
CAPACITORS Dry type of the MKP technology, mounted in upright position designed for permanent over voltage of 450V
REGULATOR Microprocessor based with switching program 1:2:4 to allow compensation of low loads. Built-in automatic rotation of capacitor sequence
ENCLOSURE Electrogalvanized sheet steel, polyester powder coated to RAL 7032
CABLING Top or Bottom
TEMPERATURE 50oC