LosAngeles GMT London Cairo Riyadh Dubai India Tokyo Sydney
HOME
HISTORY
MAIN SUPPLIERS
PROJECTS

  



Click on image to zoom
[click here to zoom ]

Manufactured to IEC 439-1
Separation up to FORM 4,
Type 1 to 7

  • Rating from 63A to 2500A
  • Panels for front access or front/rear access construction
  • Type tested for 80kA/1sec 50kA/1 sec, 50kA/3 secs
  • Starters designed for Type2 coordination
  • Draw-out or fixed pattern
  • Ample cabling space for easy connections
  • Top and bottom cable entry
  • Protection class IP 31 to IP 54
  • Ambient temperature rating 50° C
  • Factory built to client's specifications

TECHNICAL DATA

INCOMER ACB, 3-pole or 4-pole, 630 to 2500A, 65 to 85kA, fixed or drawout pattern, manual or motor operated
MCCB, 3-pole or 4-pole, 100 to 1600A, 50 to 85kA, fixed or plug-in pattern, manual or motor operated
Fuse switch 63A to 800A, 3-pole or 4-pole
Load break switch 63A to 1600A, 3-pole or 4-pole
OUTGOINGS MCCB, 3-pole or 4-pole, up to 1600A, 30 to 85kA
Fuse switches 3-pole, up to 800A, 100kA
Starters can be equipped as DOL, Y- , auto transformer, soft start or variable frequency drive starter
BUS BARS H.C.H.D. copper, electrolytically tinned and colour coded
ENCLOSURE Electrogalvanized sheet steel 2 mm, polyester powder coated to RAL 7032 textured, with removable rear covers, extendable on either side.
CABLING Removable gland plates on top and bottom, non-ferrous type for single core cables, punched to client's requirements
Termination for up to 4 cables per phase can be provided
Click on image to zoom
[click here to zoom ]