LosAngeles GMT London Cairo Riyadh Dubai India Tokyo Sydney
HOME
HISTORY
MAIN SUPPLIERS
PROJECTS

  



Click on image to zoom
[click here to zoom ]

Manufactured to IEC 439-1
Separation up to Form 4, Type 1 to 7

  • Rating 630 A to 6300 A
  • Panels for front access or front/rear access construction
  • Type tested for 80kA/1 sec, 50kA/3 sec
  • Ample cabling space for easy connections
  • Top and bottom cable entry.
  • Protection class IP 3 1 to IP 54
  • Ambient temperature rating 50° C
  • Factory built to client's specifications.

TECHNICAL DATA

INCOMER ACB, 3-pole or 4-pole, 630 to 6300A, 65 to 85kA, fixed or drawout pattern, manual or motor operated
MCCB, 3-pole or 4-pole, 630 to 1600A, 50 to 85kA, fixed or plug-in pattern, manual or motor operated.
Load break switch 630A to 1600A, 3-pole or 4-pole
BUS COUPLER ACB or MCCB as above
Electrical and/or mechanical interlocking between incomers and bus coupler can be provided, as well as various protection, tripping and indicating functions.
OUTGOINGS ACBs as above
MCCBs, 3-pole or 4-pole, up to 1600A, 30 to 85kA Fuse switches 3-pole, up to 800A, 100kA
BUS BARS H.C.H.D. copper, electrolytically tinned and colour coded
ENCLOSURE Electrogalvanized sheet steel 2 mm, polyester powder coated to RAL 7032 textured, with removable rear covers, extendable on either side.
CABLING Removable gland plates on top and bottom, non-ferrous type for single core cables, punched to client's requirements.
Termination for up to 4 cables per phase can be provided
Click on image to zoom
[click here to zoom ]
Click on image to zoom
[click here to zoom ]