| LosAngeles |
GMT |
London |
Cairo |
Riyadh |
Dubai |
India |
Tokyo |
Sydney |
|
|
|
|
|
|
|
|
|
|
|
|
 |
|
[click
here to zoom ]
|
Manufactured
to IEC 439-1
Separation to FORM 2,
Type 1 and 2
-
Rating
630A to 6300A
-
Front
access for operation and connections
-
Short circuit tested for 50kA/3 secs
-
Ample cabling space for easy connections
-
Top and bottom cable entry
-
Protection class IP 3 1 to IP 54
-
Ambient temperature rating 50° C
-
Factory built to client's specification
|
TECHNICAL
DATA
| INCOMER |
ACB,
3-pole or 4-pole, 630 to 6300A, 65 to 85kA,
draw out pattern, manual or motor operated.
MCCB, 3-pole or 4-pole, 630 to 2500A, 50 to
85kA, fixed or plug-in pattern, manual or motor
operated
Load break switch 630 A to 1600A, 3-pole or
4-pole |
| BUS
COUPLER |
ACB
or MCCB as above
Electrical and/or mechanical interlocking between
incomer and bus coupler can be provided, as
well as various protection, tripping and indicating
functions |
| OUTGOINGS |
ACBs
as above
MCCBs, 3-pole or 4-pole, up to 1600A, 30 to
85kA Fuse switches 3-pole, up to 800A, 100kA
|
| BUS
BARS |
H.C.H.D.
copper, electrolytically tinned and colour coded |
| ENCLOSURE |
Electrogalvanized
sheet steel polyester powder coated to RAL 7032
textured, with removable rear covers, extendable
on either side |
| CABLING |
Removable
undrilled gland pates on top and bottom, non-
ferrous type for single core cables, punched
to clients requirements
Termination for up to 4 cables per phase can
be provided. |
|
[click